Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
Case Number - T16DV01033
Inspection Description - INSP - INITIAL CODE ENFORCMENT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/25/2016 | INSP - INITIAL CODE ENFORCMENT | Approved | THE MASTER METERED SYSTEM WAS SUPPORTED BY AN EXISTING WOOD POST SUPPORT SYSTEM THAT WAS REPLACED WITH A NEW PERMANENT STEEL TUBULAR SUPPORT SYSTEM. THE ELECTRICAL EQUIPMENT IS A 400 AMP MASTER METERED SYSTEM WITH TWO 200 AMP PANELS ADJACENT TO THE METER LOCATION. THE ELECTRICAL VIOLATIONS ARE AS FOLLOWS: 1. TTHE NORTH PANEL HAS 4 DISCONNECTING MEANS THE SOUTH PANEL HAS 4 DISCONNECTING MEANS. THIS IS MORE THAN THE ALLOWABLE 6 DISCONNECTING MEANS FOR A SERVICE. 2. THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON EITHER PANEL. 3. BROKEN PANEL COVER ON THE NORTH PANEL, MISSING HARE WARE. 4. MULTIPLE WIRE TERMINATIONS IN THE SAME TERMINAL LUG ON THE NORTH AND SOUTH 200 AMP DISCONNECTS. 5. TWO NEW SINGLE POLE 20 AMP CIRCUIT BREAKERS HAVE BEEN INSTALLED AND WIRED TO A DOUBLE GANG RECEPTACLE OUTLET BOX. |