Case Details

Status:

COMPLIAN

Type:

WORK WITHOUT PERMITS-RESIDENTL
Address:

Entered Date:

02/26/2016

Applicant:

PLACITA DEL ARROYO LLC ATTN; GLENN A HARMON

Description:

MASTER METER SYSTEM VIOLATIONS

Case Violations

Case Number: T16DV01033
Case Status: COMPLIAN
Case Description: WORK WITHOUT PERMITS-RESIDENTL
Total Violations: 1
Violation Date Code Statue
02/26/2016 T.C. Ch. 16, Sec. 16-4. PERMITS REQUIRED. Unless otherwise exempt pursuant to section 301 of the Administrative Code, as adopted by reference per section 6-1 of this Code, or pursuant to any other ordinance or statute, no building, structure or building service equipment regulated by this chapter or by the technical codes adopted by the city shall be built, erected, constructed, enlarged, altered, repaired, moved, improved, removed, converted or demolished unless a permit first has been obtained from the building official in the manner provided in the administrative and building codes adopted by the city. The purpose of a permit is to ensure that all construction is inspected by qualified City of Tucson personnel as directed by ordinance to verify compliance with city codes. Failure to obtain proper permit with inspections and approvals shall deem the construction to be unsafe.

Outstanding Inspections

Case Number: T16DV01033
Case Status: COMPLIAN
Case Description: WORK WITHOUT PERMITS-RESIDENTL
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
08/11/2016 NPO(EL)-MAIN/PANEL/SUB/DISCONT VALDEZ Item closed

Completed Inspections

Case Status: COMPLIAN
Case Number: T16DV01033
Case Description: WORK WITHOUT PERMITS-RESIDENTL
Total Completed Inspections - 2
End Date Description Inspector Results Comments
02/25/2016 INSP - INITIAL CODE ENFORCMENT VALDEZ Approved THE MASTER METERED SYSTEM WAS SUPPORTED BY AN EXISTING WOOD POST SUPPORT SYSTEM THAT WAS REPLACED WITH A NEW PERMANENT STEEL TUBULAR SUPPORT SYSTEM. THE ELECTRICAL EQUIPMENT IS A 400 AMP MASTER METERED SYSTEM WITH TWO 200 AMP PANELS ADJACENT TO THE METER LOCATION. THE ELECTRICAL VIOLATIONS ARE AS FOLLOWS: 1. TTHE NORTH PANEL HAS 4 DISCONNECTING MEANS THE SOUTH PANEL HAS 4 DISCONNECTING MEANS. THIS IS MORE THAN THE ALLOWABLE 6 DISCONNECTING MEANS FOR A SERVICE. 2. THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON EITHER PANEL. 3. BROKEN PANEL COVER ON THE NORTH PANEL, MISSING HARE WARE. 4. MULTIPLE WIRE TERMINATIONS IN THE SAME TERMINAL LUG ON THE NORTH AND SOUTH 200 AMP DISCONNECTS. 5. TWO NEW SINGLE POLE 20 AMP CIRCUIT BREAKERS HAVE BEEN INSTALLED AND WIRED TO A DOUBLE GANG RECEPTACLE OUTLET BOX.
08/11/2016 INSP - FOLLOW UP CODE ENFORCE VALDEZ Approved PERMIT T13CM05038 IS ACTIVE STATUS PER SUPERVISION WILL CLOSE CASE

Completed Activity Special Conditions

Case Description - WORK WITHOUT PERMITS-RESIDENTL
Case Number - T16DV01033
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 5
Date Name
03/16/2016 CONTACTED BY PHONE
02/26/2016 CONTACTED IN PERSON
03/16/2016 CONTACTED BY MAILING
10/28/2016 NOTICE OF VIOLATION ISSUED
08/11/2016 VIOLATION CLOSED