Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T16CM08309
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/27/2017 | FIRE - FINAL | Approved | ||
11/02/2017 | FIRE - FINAL | Partial Approval | 1) Need separate permit for sprinkler that was moved/relocated into new HVAC closet. This work was done without permits and not by a licensed sprinkler contractor. 2) Correct sprinkler coverage under soffit in dining room. 3) Repair/correct sprinkler heads under soffit and sidewalls. Some are too far into drywall. 4) Also need separate permit for any other relocates or adding of sprinklers. Work needs to be done by a licensed sprinkler contractor. |