Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T16CM07308
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/05/2019 | FIRE - FINAL | Approved | Per MAshford the phones provided at the elevator landings meet the intent of the two way communication. HSL knows that if they remove the phones they will no longer be code compliant. Tested the ERRC today and everything passed. Approved for C of O |
|
05/02/2019 | FIRE - FINAL | Partial Approval | APPROVED FOR TCO TO OCCUPY AND OPEN TO PUBLIC Need to complete the ERRC for COFO Need to complete the 2-way for COFO |
|
04/30/2019 | FIRE - FINAL | Partial Approval | Need the two-way communication Need to install the ERRC system since the building failed the test Need the address on the north side of the building Exit signs need to be every 100' East and West side stairwells need exterior signs Need a RISER ROOM sign and (3) FACP Signs installed Locked all the keys in the KNOX boxes Locked the elevator keys in the KNOX box Tested water flow and tamper on the fire alarm system Tested emergency and exit lights |