Permit: T16CM07308

Parcel: 141220250


Addresses:

9095 S RITA RD

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
05/07/2019 PLUMBING - INTERMEDIATE Approved
04/29/2019 PLUMBING - INTERMEDIATE Partial Approval 3rd floor rooms ok for occupancy upon c of o
01/09/2019 PLUMBING - INTERMEDIATE Partial Approval update entry only
12/18/2018 PLUMBING - INTERMEDIATE Approved 3rd floor, 8 rooms ok east side of building.
12/14/2018 PLUMBING - INTERMEDIATE Partial Approval Pex water lines 3rd Floor Ok
12/05/2018 PLUMBING - INTERMEDIATE Partial Approval All guest rooms on the second floor, west of elevator, OK to rock.
12/04/2018 PLUMBING - INTERMEDIATE Partial Approval 3rd floor tub drains ok to cover.
11/30/2018 PLUMBING - INTERMEDIATE Not ready for Inspection WORK INCOMPLETE
11/14/2018 PLUMBING - INTERMEDIATE Partial Approval 1- 2nd floor west of the elevator shaft to the end of bldg plumbing DWV water test and overhead and in wall domestic water distribution is okay to cover.
11/08/2018 PLUMBING - INTERMEDIATE Partial Approval 1- Entire second floor DWV system and tubs water test provided
2- Overhead and in wall Domestic water distribution from east of the elevator shaft to end of bldg is okay, hydrostatic pressure test provided.
09/25/2018 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1- FIRST FLOOR GUEST ROOMS DWV SYSTEM AND OVERHEAD AND IN WALL DOMESTIC WATER DISTRIBUTION IS OKAY TO COVER.
2- DWV WATER TEST PROVIDED.
09/07/2018 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1- SHALL PROVIDE CLEAN OUTS AT THE BASE OF ALL WASTE AND SOIL STACKS AND VENT STACKS.
2- THREADED FITTINGS CAN NOT BE LOCATED IN A CONCEALED LOCATION.
05/08/2018 PLUMBING - INTERMEDIATE Not ready for Inspection