Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/10/2017 | FRAMING | Approved | ||
| 12/19/2016 | FRAMING | Denied | 1. HEADERS IN BEARING WALLS MUST BE DOUBLE 2X6 MIN. 2. ADD FOOTINGS AT 2X6 BEARING WALLS. 3. CAMERA UNDERGROUND PLUMBING WITH INSPECTOR PRESENT. PROVIDE TEST ON DWV SYSTEM. 4. EXPOSE UNDERGROUND PLUMBING OUTSIDE OF BUILDING. 5. RE-NAIL ROOF PLYWOOD IN ADDITION. |
|
| 09/08/2016 | FRAMING | Denied | 1. ROOF WAS COVERED WITHOUT INSPECTION. 2. WALL SUPPORTING SOUTH END OF OLD JOISTS IS NOW BEARING. THEREFORE, IT WILL REQUIRE A FOOTING AND DOUBLE TOP PLATE AS WELL AS HEADERS AT DOOR OPENINGS. |
|
| 08/24/2016 | FRAMING | Not ready for Inspection | ZONING APPROVAL FOR CONVERSION OF GARAGE TO SLEEPING QUARTERS IS REQUIRED DUE TO NON-COMPLIANT SETBACKS. |