Permit: T16CM02856

Parcel: 12404100A


Addresses:

930 E 2ND ST


Inspection Status: Approved

Inspection History: SHEET ROCK NAILING

Permit Number - T16CM02856

Inspection Description - SHEET ROCK NAILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/20/2020 SHEET ROCK NAILING Approved
04/30/2020 SHEET ROCK NAILING Partial Approval Partial. Stairwell #3; Levels 2-14. Ok to tape progress areas.
04/28/2020 SHEET ROCK NAILING Partial Approval Partial. Level #7 (Burn area corridor). Ok to tape walls and ceiling.
04/28/2020 SHEET ROCK NAILING Partial Approval Partial. Level #7 (Burn area corridor). Ok to tape walls and ceiling.
04/24/2020 SHEET ROCK NAILING Not ready for Inspection No contact information to schedule inspection.
04/21/2020 SHEET ROCK NAILING Partial Approval Level #6 (Burn area); Rooms #630; 631; 632; 633; 634; 634. Ok to tape progress areas.
04/16/2020 SHEET ROCK NAILING Partial Approval RVI Level #5; Rooms #531; 532; 533; 534; 536. Ok to tape progress areas.
04/14/2020 SHEET ROCK NAILING Partial Approval RVI Level #4; Burn Area, Rooms 430; 431; 432; 433; 434; 436. Ok to tape progress areas.
04/08/2020 SHEET ROCK NAILING Not ready for Inspection RVI Contractor cancelled.
04/06/2020 SHEET ROCK NAILING Partial Approval RVI-Levels #9 and #10; corridor walls and ceilings. Ok to tape progress areas.
03/20/2020 SHEET ROCK NAILING Not ready for Inspection Contractor cancelled.
03/19/2020 SHEET ROCK NAILING Partial Approval Level#10; Rooms: 1000; 1001; 1003; 1005; 1007; 1009; 1010; 1011; 1012. Ok to,tape progress areas.
03/18/2020 SHEET ROCK NAILING Partial Approval Level #12; Rooms 1200; 1201 top-out sheetrock at 18” below deck above. Ok to tape progress areas.
03/17/2020 SHEET ROCK NAILING Partial Approval Level #9; Rooms: 900; 901; 902; 903; 905; 907; 909; 910; 911; 912. Ok to tape progress.
03/13/2020 SHEET ROCK NAILING Partial Approval Level #8; Corridor walls and ceiling. Ok to tape progress areas.
03/12/2020 SHEET ROCK NAILING Partial Approval Level #8; Rooms: 800; 801; 803; 805. Ok to tape progress areas.
03/11/2020 SHEET ROCK NAILING Not ready for Inspection Canceled by contractor.
03/10/2020 SHEET ROCK NAILING Partial Approval Level#15; South Elevator Lobby #1561; shafts all 2 hour rated with 2 layers of sheetrock
03/09/2020 SHEET ROCK NAILING Partial Approval North elevator shafts; West side: Levels #14 to basement. Taped and fire caulked.
03/06/2020 SHEET ROCK NAILING Partial Approval Top-out sheetrock at 18" from deck above: Level #5; 530; 531; 532; 533; 534; 536. Level #12; 1211; 1230; 1231; 1232; 1236. Ok to tape progress areas.
NOTE: At approximately 1000 hours, a tool gang box from CECO Concrete fell from level #14; Southwest area. The box impacted in the street between The Collective and the Marriott Hotel. No injuries were sustained and the proper authorities were notified. The box was removed and work in the area continued. Cause of the falling box is unknown to this Inspector at thIs time,
03/04/2020 SHEET ROCK NAILING Partial Approval Level #12; corridor #1260; top-out sheetrock at 18" below deck above.
02/28/2020 SHEET ROCK NAILING Partial Approval Level #7; Rooms: 700; 702; 707; 709; 710. Ok to tape progress areas.
02/27/2020 SHEET ROCK NAILING Partial Approval Level #15; Elevator shaft exterior wall sheathing on North and West walls.
02/26/2020 SHEET ROCK NAILING Not ready for Inspection Contractor cancelled
02/25/2020 SHEET ROCK NAILING Partial Approval Level #6; Rooms: 600; 601; 602; 603; 605; 607; 609; 610; 619. Ok to tape progress areas.
02/24/2020 SHEET ROCK NAILING Partial Approval Top-out sheetrock at 18" below above decking at Level #11; Rooms: 1100; 1101; 1102; 1103; 1105; 1107; 1109; 1110; 1112; 1163; 1164.
Level #9; Rooms: 900; 901; 902; 903; 904; 905; 907; 909; 910; 911; 912
02/21/2020 SHEET ROCK NAILING Partial Approval Rock ok to tape in units 613, 611, 612
02/20/2020 SHEET ROCK NAILING Not ready for Inspection Contractor cancelled
02/19/2020 SHEET ROCK NAILING Partial Approval Level #6; Rooms: 617; 619; 620; 621; 622. Ok to tape progress areas.
02/14/2020 SHEET ROCK NAILING Not ready for Inspection Canceled
02/13/2020 SHEET ROCK NAILING Partial Approval Level #9; top-out at 18” below the deck above: Rooms: 900; 901; 902; 903; 904; 905; 907; 909; 910; 911; 912; 965; Corridor #960. Ok to tape progress areas.
02/12/2020 SHEET ROCK NAILING Partial Approval Level #8; Rooms: 800; 801; 802; 803; 804; 805; 807; 809; 810; 811; 812. Top out sheetrock at 18" below deck above. Ok to tape progress areas.
02/11/2020 SHEET ROCK NAILING Not ready for Inspection Contractor cancelled.
02/10/2020 SHEET ROCK NAILING Partial Approval Level #3; corridor #360; Level #4; Corridor #460; Level #5; corridor #560. Level #5 Rooms: 500; 501; 502; 503; 505; 507; 509; 511; 512; 513. Ok to tape progress areas
02/07/2020 SHEET ROCK NAILING Partial Approval Level #5; Rooms: 513; 517; 518; 519; 521; 520; 522. Ok to tape progress areas.
02/06/2020 SHEET ROCK NAILING Partial Approval Level #6; top-out sheetrock at 24" from deck above; corridor #650 and west side rooms. Ok to tape progress areas.
02/05/2020 SHEET ROCK NAILING Not ready for Inspection Contractor cancelled.
02/04/2020 SHEET ROCK NAILING Not ready for Inspection Contractor cancelled.
01/31/2020 SHEET ROCK NAILING Partial Approval Top-out sheetrock nailing at 24" below deck above at Level#9: corridor 960 (North to South student side).
01/30/2020 SHEET ROCK NAILING Not ready for Inspection Contractor cancelled.
01/27/2020 SHEET ROCK NAILING Not ready for Inspection Contractor cancelled.
01/24/2020 SHEET ROCK NAILING Not ready for Inspection Contractor cancelled.
01/22/2020 SHEET ROCK NAILING Partial Approval Level #4; Rooms 401; 403; 405; 417; 419; 421; 422. Ok to tape progress areas.
01/17/2020 SHEET ROCK NAILING Not ready for Inspection
01/16/2020 SHEET ROCK NAILING Not ready for Inspection Per super
01/15/2020 SHEET ROCK NAILING Partial Approval Top-out sheetrock at 18” below deck above at Level #5; Rooms: 500; 501; 502; 503; 504; 505; 507; 509; 510; 511; 512; 513; 517; 518; 519; 520; 521; 522.
01/14/2020 SHEET ROCK NAILING Not ready for Inspection Contractor cancelled.
01/13/2020 SHEET ROCK NAILING Partial Approval Level. #5 Corridor #560: North, East, West Sections.
01/10/2020 SHEET ROCK NAILING Partial Approval Level #3; Room 315. Ok to tape progress areas
01/09/2020 SHEET ROCK NAILING Partial Approval Level #4, top out Sheetrock at 18 below deck above; room #404; 402. Sheetrock in rooms; Level #3; Rooms 309; 310; 348; 350; 354. Ok to tape progress areas.
01/07/2020 SHEET ROCK NAILING Partial Approval Level #3; Rooms: 300; 301; 305; 307; 303; 340; 342.
01/06/2020 SHEET ROCK NAILING Partial Approval Level #3; Rooms: 311; 313; 317; 317; 319; 321; 322. Ok to tape progress areas.
01/02/2020 SHEET ROCK NAILING Partial Approval Level#4; Top out at 18 inches from deck above in rooms, 422; 430; 431; 433; 434; 436. Ok to tape progress areas.
12/30/2019 SHEET ROCK NAILING Partial Approval Level #2 , Rooms 246; 344. Ok to tape progress areas.
12/24/2019 SHEET ROCK NAILING Partial Approval Level #2; Room 200. Ok to tape progress areas.
12/20/2019 SHEET ROCK NAILING Partial Approval Level #2; Rooms 201; 203; 240; 242; 348; 350; 252; 354; 255. Ok to tape progress areas
12/19/2019 SHEET ROCK NAILING Not ready for Inspection Contractor cancelled.
12/18/2019 SHEET ROCK NAILING Not ready for Inspection Contractor cancelled.
12/17/2019 SHEET ROCK NAILING Cancelled Contractor cancelled, reschedule for 18 December.
12/16/2019 SHEET ROCK NAILING Not ready for Inspection
12/13/2019 SHEET ROCK NAILING Not ready for Inspection Contractor cancelled. Level #3; Room 309.
12/12/2019 SHEET ROCK NAILING Partial Approval Level #4; Rooms 400; 401; 405; 411; 413 top-out at 18” below deck above. Ok to tape progress areas.
12/10/2019 SHEET ROCK NAILING Partial Approval Level #3 top-out at 30' below deck above in rooms: 300; 301; 303; 305; 307; 309; 340; 342; 344; 348; 349; 351. Ok to tape progress areas.
12/09/2019 SHEET ROCK NAILING Partial Approval Level #3; top out rooms at 30” below above deck: Rooms 310; 318; 350. Level #4; top out rooms at 18” below above deck: 415; 417; 419; 421.
12/06/2019 SHEET ROCK NAILING Not ready for Inspection Contractor cancelled
12/05/2019 SHEET ROCK NAILING Not ready for Inspection Contractor cancelled
12/03/2019 SHEET ROCK NAILING Not ready for Inspection Contractor cancelled.
12/02/2019 SHEET ROCK NAILING Not ready for Inspection Contractor cancelled.
11/26/2019 SHEET ROCK NAILING Partial Approval Level #3; Rooms: Electric Room #374; IDF Room #373; Shaft #360 and 366. Ok to tape progress areas.
11/22/2019 SHEET ROCK NAILING Not ready for Inspection Contractor cancelled.
11/21/2019 SHEET ROCK NAILING Not ready for Inspection Contractor cancelled.
11/20/2019 SHEET ROCK NAILING Not ready for Inspection Contractor cancelled.