Inspection Status: Approved
Inspection History: BUILDING - PROGRESS
| Date |
Description |
Inspector |
Results |
Comments |
| 12/26/2017 |
BUILDING - PROGRESS |
|
Approved |
|
| 10/27/2016 |
BUILDING - PROGRESS |
|
Partial Approval |
PLUMBING UNDERGROUND: STORM DRAIN LINES AT GL: AW - CW/ 2.5 - 3.5. OK TO COVER PROGRESS AREA. |
| 10/17/2016 |
BUILDING - PROGRESS |
|
Partial Approval |
ELECTRIC UNDERGROUND; AT GL: BW.2- CW/ 1; APPROXIMATELY 75' WITH 2 EACH 4" CONDUITS, 3 EACH 1 1/2" CONDUITS; BW.5/ 1 - 2 APPROXIMATELY 50' WITH 2 EACH 4" CONDUITS, 3 EACH 1 1/2" CONDUITS. OK TO COVER PROGRESS AREAS. |
| 10/11/2016 |
BUILDING - PROGRESS |
|
Partial Approval |