Permit: T16BU01049

Parcel: 11310001A


Addresses:

1545 E COPPER ST 04


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T16BU01049

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/21/2016 FIRE - ALARM FINAL Approved as builds under permit # t16fc00140
10/05/2016 FIRE - ALARM FINAL Partial Approval 1) West gymnasium notification devices not functioning on alarm that is initiated from Central Alarms side.
2) Verify AC out 'trouble' on "Advanced" System panel is either within delay time for an AC fail ( per NFPA 72) or there if it was a problem with a relay.