Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T16BU01049
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/21/2016 | FIRE - ALARM FINAL | Approved | as builds under permit # t16fc00140 | |
| 10/05/2016 | FIRE - ALARM FINAL | Partial Approval | 1) West gymnasium notification devices not functioning on alarm that is initiated from Central Alarms side. 2) Verify AC out 'trouble' on "Advanced" System panel is either within delay time for an AC fail ( per NFPA 72) or there if it was a problem with a relay. |