Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2016 | FIRE SPKLR - FINAL | Approved | ||
| 06/03/2016 | FIRE SPKLR - FINAL | Partial Approval | 1) need gauges on riser 2) need mani drain test 3) install missing heads, some pendent drops still plugged 4) sidewalls on patio blocked 5) head too far from wall, west exit door, upright 6) heads taped/covered (painters) 7) escutcheons |