Inspection History: FIRE SPKLR - OH PIPING & HYDRO
Permit Number - T16BU00445
Inspection Description - FIRE SPKLR - OH PIPING & HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/07/2016 | FIRE SPKLR - OH PIPING & HYDRO | Approved | ||
05/20/2016 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | hydro approved. upright closest to west door is >10' from wall. cooler and freezer walls need to have walls to ceiling or add heads. currenly no walls so need to add heads. | |
04/27/2016 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | Ok to place hard lid and drywall |