Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date |
Description |
Inspector |
Results |
Comments |
| 03/05/2015 |
INSP - INITIAL CODE ENFORCMENT |
|
Approved |
VISITED SITE, ALLEGRIA APTS. FORMALLY PUEBLO VILLAS. MET WITH TFD CAPTAIN WHO EXPLAINED THAT A MOTHER AND CHILDREN HAD JUST PARKED CAR, SIX YEAR OLD DAUGHTER GOT OUT OF THE CAR STOOD ON THE CODUIT ATTACHED TO THE WALL AND GOT A SHOCK. INSPECTING THE ISSUE I FOUND A JUNCTION THAT CONNECTED CONDUIT TO A LIGHT POLE, THE CONDUIT HAD BEEN PROPERLY ATTACHED TO THE WALL WITH CLIPS 4 FT ON CENTER AND CONDUIT DISCONNECTED AT THE COUPLING, AND EVIDENCED THAT THE CONDUIT WAS AT LEAST A 1/2" INTO THE COUPLING. WIRE HAD ARCHED WITH IN THE COUPLING/CONDUIT AND APPEARED TO BE STEPPED ON DUE TO 4 OR 5 OF THE CLIPS ATTACHING CONDUIT TO THE WALL BEING BENT OVER.WENT TO UNIT C-1015 BUT FOUND AN ELDERLY TENNANT UNAWARE OF THE SITUATION. WENT TO THE OFFICE, FOUND OFFICE CLOSED AND TRIED CONTACTING MAINTANENCE, DID LEAVE A MESSAGE. RECEIVED CALL BACK FROM MIKE, MAINTENANCE SUPERVISOR, WE MADE ARRANGEMENTS TO MEET ON SITE THE FOLLOWING MORNING AS I FELT IT WAS NOT AN EMERGENCY DUE TO NO ARCHING OR SHOCK TO TOUCH. PLACED TO CONES AND EMERGENCY- CAUTION TAPE FROM CONE TO CONE IN FRONT OF THE JUNCTION BOX THAT FED THE LIGHT POLE. |