Status:

COMPLIAN

Type:

EMERGENCY
Address:

Entered Date:

03/06/2015

Applicant:

PUEBLO VILLAS APARTMENTS LLC

Description:

ELECTRICAL ISSUE

Outstanding Inspections

Case Number: T15DV01700
Case Status: COMPLIAN
Case Description: EMERGENCY
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
03/10/2015 NPO(EL)-WIRING/SWITCH/OUTLT/FX GOODMAN Item closed

Completed Inspections

Case Status: COMPLIAN
Case Number: T15DV01700
Case Description: EMERGENCY
Total Completed Inspections - 2
End Date Description Inspector Results Comments
03/05/2015 INSP - INITIAL CODE ENFORCMENT GOODMAN Approved VISITED SITE, ALLEGRIA APTS. FORMALLY PUEBLO VILLAS. MET WITH TFD CAPTAIN WHO EXPLAINED THAT A MOTHER AND CHILDREN HAD JUST PARKED CAR, SIX YEAR OLD DAUGHTER GOT OUT OF THE CAR STOOD ON THE CODUIT ATTACHED TO THE WALL AND GOT A SHOCK. INSPECTING THE ISSUE I FOUND A JUNCTION THAT CONNECTED CONDUIT TO A LIGHT POLE, THE CONDUIT HAD BEEN PROPERLY ATTACHED TO THE WALL WITH CLIPS 4 FT ON CENTER AND CONDUIT DISCONNECTED AT THE COUPLING, AND EVIDENCED THAT THE CONDUIT WAS AT LEAST A 1/2" INTO THE COUPLING. WIRE HAD ARCHED WITH IN THE COUPLING/CONDUIT AND APPEARED TO BE STEPPED ON DUE TO 4 OR 5 OF THE CLIPS ATTACHING CONDUIT TO THE WALL BEING BENT OVER.WENT TO UNIT C-1015 BUT FOUND AN ELDERLY TENNANT UNAWARE OF THE SITUATION. WENT TO THE OFFICE, FOUND OFFICE CLOSED AND TRIED CONTACTING MAINTANENCE, DID LEAVE A MESSAGE. RECEIVED CALL BACK FROM MIKE, MAINTENANCE SUPERVISOR, WE MADE ARRANGEMENTS TO MEET ON SITE THE FOLLOWING MORNING AS I FELT IT WAS NOT AN EMERGENCY DUE TO NO ARCHING OR SHOCK TO TOUCH. PLACED TO CONES AND EMERGENCY- CAUTION TAPE FROM CONE TO CONE IN FRONT OF THE JUNCTION BOX THAT FED THE LIGHT POLE.
03/10/2015 INSP - FOLLOW UP CODE ENFORCE GOODMAN Approved FOLLOW UP INPSECTION FOUND CONDUIT AT THE COUPLING REPAIRED, CLIPS ATTACHING THE CONDUIT REPLACED AND WIRING FROM THE LIGHT POLE TO THE JUNCTION BOX REPLACED. COMPLIANCE / CLOSE CASE.

Completed Activity Special Conditions

Case Description - EMERGENCY
Case Number - T15DV01700
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 3
Date Name
03/26/2015 CONTACTED IN PERSON
03/26/2015 NOTICE OF VIOLATION ISSUED
11/28/2016 VIOLATION CLOSED

Documents

File Name Document Type  
520 W. PRINCE RD NOV.PDF DOCUMENTS VIEW