Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T15CM08230
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/05/2018 | FIRE - FINAL | Approved | ||
04/24/2018 | FIRE - FINAL | Denied | Remove east side restroom exit sign East side empty service storage room fire sprinkler head needs to be lowered so that the escutcheon fits properly East side storage room needs to have the sprinkler head lowered to below 1" depth East side storage needs to have the damper removed along with sampling tube and duct detector Mag locks on both concourses need to be interconnected to the fire alarm and unlock on a general alarm Concourse doors need to have signs that read "Emergency Exit Only" East side electrical vault fire alarm modifications need to be submitted and permitted with TFD Fly bar storage electrical, fire wire and data cabling needs to be installed in a clean workmanship like manner Fire damper abandoned in concourse A electrical room needs to be removed and the wall needs to be completed. Fire alarm needs to be tested at 100% of all devices and a report provided to the AHJ. Exit signs need to be installed B side international area Exit signs need to be installed at the exit doors bottom of both concourses. Pay re-inspection fees prior to calling back in the fire final |