Permit: T15CM08230

Parcel: 140420120


Addresses:

7005 S PLUMER AV


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T15CM08230

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/05/2018 FIRE - FINAL Approved
04/24/2018 FIRE - FINAL Denied Remove east side restroom exit sign
East side empty service storage room fire sprinkler head needs to be lowered so that the escutcheon fits properly
East side storage room needs to have the sprinkler head lowered to below 1" depth
East side storage needs to have the damper removed along with sampling tube and duct detector
Mag locks on both concourses need to be interconnected to the fire alarm and unlock on a general alarm
Concourse doors need to have signs that read "Emergency Exit Only"
East side electrical vault fire alarm modifications need to be submitted and permitted with TFD
Fly bar storage electrical, fire wire and data cabling needs to be installed in a clean workmanship like manner
Fire damper abandoned in concourse A electrical room needs to be removed and the wall needs to be completed.
Fire alarm needs to be tested at 100% of all devices and a report provided to the AHJ.
Exit signs need to be installed B side international area
Exit signs need to be installed at the exit doors bottom of both concourses.
Pay re-inspection fees prior to calling back in the fire final