Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date |
Description |
Inspector |
Results |
Comments |
| 07/01/2015 |
MECHANICAL - HOODS |
|
Approved |
IVRS - Inspection :* |
| 06/26/2015 |
MECHANICAL - HOODS |
|
Partial Approval |
OK FOR PARTIAL TILES IN KITCHEN ACCESS DOORS STILL NOT BUILT PER INSTALL INSTRUCTIONS. TYPE 1 FANS MUST TERMINATE 10' FROM A WALL OR AT TOP OF WALL OR AT TOP OF WALL PROVIDE APPROVAL FROM CAPTIVE AIR IF ALTERING EXHUAST FANS. |
| 06/24/2015 |
MECHANICAL - HOODS |
|
Partial Approval |
BANDINGTO BE 1 1/2" FROM EACH EDGE + 10 1/2 SPACING ACCESS DOORS NOT INSULATED PER INSTALL INSTRUCTIONS BANDING MISSING IN SOME SPOTS |
| 06/19/2015 |
MECHANICAL - HOODS |
|
Partial Approval |
SMOKE TEST PASSED, OK TO DOUBLE WRAP REMAINDER OF DUCT. |