Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
Permit Number - T15CM02052
Inspection Description - MECHANICAL - HOODS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/01/2015 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* | |
06/26/2015 | MECHANICAL - HOODS | Partial Approval | OK FOR PARTIAL TILES IN KITCHEN ACCESS DOORS STILL NOT BUILT PER INSTALL INSTRUCTIONS. TYPE 1 FANS MUST TERMINATE 10' FROM A WALL OR AT TOP OF WALL OR AT TOP OF WALL PROVIDE APPROVAL FROM CAPTIVE AIR IF ALTERING EXHUAST FANS. | |
06/24/2015 | MECHANICAL - HOODS | Partial Approval | BANDINGTO BE 1 1/2" FROM EACH EDGE + 10 1/2 SPACING ACCESS DOORS NOT INSULATED PER INSTALL INSTRUCTIONS BANDING MISSING IN SOME SPOTS | |
06/19/2015 | MECHANICAL - HOODS | Partial Approval | SMOKE TEST PASSED, OK TO DOUBLE WRAP REMAINDER OF DUCT. |