Permit: T15CM02052

Parcel: 10821018Y

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
07/01/2015 MECHANICAL - HOODS Approved IVRS - Inspection :*
06/26/2015 MECHANICAL - HOODS Partial Approval OK FOR PARTIAL TILES IN KITCHEN ACCESS DOORS STILL NOT BUILT PER INSTALL INSTRUCTIONS. TYPE 1 FANS MUST TERMINATE 10' FROM A WALL OR AT TOP OF WALL OR AT TOP OF WALL PROVIDE APPROVAL FROM CAPTIVE AIR IF ALTERING EXHUAST FANS.
06/24/2015 MECHANICAL - HOODS Partial Approval BANDINGTO BE 1 1/2" FROM EACH EDGE + 10 1/2 SPACING ACCESS DOORS NOT INSULATED PER INSTALL INSTRUCTIONS BANDING MISSING IN SOME SPOTS
06/19/2015 MECHANICAL - HOODS Partial Approval SMOKE TEST PASSED, OK TO DOUBLE WRAP REMAINDER OF DUCT.