Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T15CM01699
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/30/2015 | FIRE - FINAL | Approved | aLL DOORS/WINDOWS OPEN APPROPRIATELY LOCKS ON DOORS ARE PER CODE SMOKE DETECTORS ALL TIED TOGETHER AND INITIATING ONE DEVICE ACTIVATES ALL DEVICES. APPROVED - NS 4/30/15 |
|
04/29/2015 | FIRE - FINAL | Denied | Smoke detector on hallway ceiling is supposed to be tied into all smokes. when tested ...did not cause the detector in the bedroom on the left to sound. That detector did not signal all of the other detectors to go off, either. Spoke with John George who wired them and he will fix it and call me tomorrow for time set up for inspection. Everything else was per fire code. NS - Denied |