Inspection Status: Approved
Inspection History: SITE - SEWER
| Date |
Description |
Inspector |
Results |
Comments |
| 03/27/2015 |
SITE - SEWER |
|
Approved |
IVRS - Inspection :* |
| 03/27/2015 |
SITE - SEWER |
|
Approved |
MH #1 & MH #2 PASSED MIRROR TEST, MAUDRE TEST, & MH PRESS TEST. TESTED 8" & 6" LINES W/ 4.5 PSI FOR 15 MINUTES AS REQUIRED |
| 03/19/2015 |
SITE - SEWER |
|
Partial Approval |
IVRS - Inspection :* |
| 03/19/2015 |
SITE - SEWER |
|
Partial Approval |
6" WASTE LINE FROM MANHOLE #1 - MANHOLE #2 (SDR-35) - OK TO COVER |
| 03/18/2015 |
SITE - SEWER |
|
Partial Approval |
IVRS - Inspection :* |
| 03/18/2015 |
SITE - SEWER |
|
Partial Approval |
MANHOLE #1 - 8", 6", 2 @ 4" LINES; MANHOLE #2 - 6", 2 @ 4" LINES - OK TO POUR MANHOLES - BACKFILL - ALL WASTE LINES TO MANHOLES |
| 03/16/2015 |
SITE - SEWER |
|
Partial Approval |
APPROX 200' OF 8" WASTE LINE (WITH 24" CLEAN-OUTS) WEST MAN HOLE TO EAST OK TO COVER |