Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/11/2015 | FIRE - FINAL | Approved | ||
| 05/07/2015 | FIRE - FINAL | Denied | 1. PROVIDE KEY OPERATEDLOCKS ON FRONT DOOR AND ADD SIGNAGE ABOVE DOOR "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" 2. POST MAXIMUM OCCUPANT LOAD SIGN "78" 3. PROVIDE 1-2A10BC RATED FIRE EXTINGUISHER IN DINING AREA 4. PROVIDE PROTECTIVE COVERS IN COOLER FOR SPRINKLER HEADS |