Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/11/2015 | FIRE - ALARM FINAL | Approved | ||
| 12/10/2015 | FIRE - ALARM FINAL | Partial Approval | pull station - alarm at panel - signal verified smoke - alarm - signal verified tamper - supervisory - signal verified flow - 31 sec to alarm - signal verified stobes / horn strobe - approved PROBLEMS: battery trouble not reporting signal to central station, smoke trouble not reporting signal to central station |