Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - UG PIPING FLUSH
Permit Number - T15BU00541
Inspection Description - FIRE SPKLR - UG PIPING FLUSH
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/15/2016 | FIRE SPKLR - UG PIPING FLUSH | Approved | per contractor, all UG flushed for this permit but never closed out. | |
08/19/2015 | FIRE SPKLR - UG PIPING FLUSH | Partial Approval | Flush was done for Building 'E' ( South of TJ max). Flushed for 1 min with burlap and found debris. flushed for 1 minute with out burlap - ran clean flushed an additional minute with burlap - rand clean/no debris in bag. Still need flush for buildings going up to the North and West of Dicks. |
|
07/15/2015 | FIRE SPKLR - UG PIPING FLUSH | Partial Approval | Flushed 2x 160' - 6" inch line for building #7 on the corner of broadway and wilmot 1min each time. Still need to flush UG line for the building next to TJ Max - southside. | |
05/27/2015 | FIRE SPKLR - UG PIPING FLUSH | Partial Approval | DICKS SPORTS WAS FLUSHED FOR 1 MIN ON 05.20.2015, PERMIT WAS PAID FOR ON 05.26.2015 |