Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - UG, PIPING, HYDRO
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/14/2015 | FIRE SPKLR - UG, PIPING, HYDRO | Approved | 200 PSI FOR 2 HOURS DONEON ALL UG'S | |
| 05/26/2015 | FIRE SPKLR - UG, PIPING, HYDRO | Partial Approval | DICKS SPORTS WAS TESTED 200 PSI FOR 2 HOURS ON 05.20.2015, PERMIT WAS PAID FOR ON 05.26.2015 | |
| 05/20/2015 | FIRE SPKLR - UG, PIPING, HYDRO | Denied | Need permit for Dicks sports, TJ Max, and property next to TJ Max. Lines that were on permit had only 150 & 180 pressure need 200 for 2 hours. |