Case: T14DV06220

Parcel: 138100520


Addresses:

110 E DELTA RD

Inspection Status: Approved

Inspection History: INSP - FOLLOW UP CODE ENFORCE

Date Description Inspector Results Comments
08/22/2014 INSP - FOLLOW UP CODE ENFORCE Approved RECEIVED CALL FROM ANGEL VILLALBA WHO STATED HE DID CHECK LOADS ON ALL BREAKERS, STATED THAT THE SMOKE SMELL INSIDE CAME FROM A OLD MOTOR IN THE COOLER, CHANGED OUT THE MOTOR FOR A NEW ONE AND CHECKED THAT COOLER WAS NOW RUNNING PROERLY. BREAKERS WERE CHANGED OUT FOR PROPER BREAKERS.
** CALLED AND SPOKE TO RICK H TO DETERMINE IF A PERMIT WOULD BE REQUIRED FOR ANYTHING, RICK SAID NO. CALLED AND SPOKE TO OCCUPANTS WHO CONFIRMED THE WORK THAT WAS DONE. ISSUE ABATED. COMPLIANCE / CLOSE CASE.
08/20/2014 INSP - FOLLOW UP CODE ENFORCE Approved MET WITH PROPERTY MANAGER QUAY, MYSELF, RICK HOLLINGER, AND ELECTRICAIN ANGEL (ENERGY SOURCE ELECTRICAL) RICK HOLLINGER KNEW ANGEL, MENTIONED HE WAS A RELIABLE ELCTRICIAN. ALL CHECKED THE MAIN SERVICE PANEL ON THE EXTERIOR OF THE STRUCTURE, FOUND NO PROBLEMS WITH THE PANEL. THEN CHECKED THE INTERIOR SUB PANEL, POINTED OUT THE MIXED BREAKERS, RICK H NOTED THE TRIPPED BREAKER WAS ALSO SERVING AS A GROUND FOR THE GFI'S ( RICK NOTED IT WAS THE SAME AS GROUNDING THE GROUND. ANGEL STATED HE WOULD NEED TO REPLACE THE TRIPPED BREAKER AND CHECK THE LOAD ON THE REMAINING BREAKERS. RICK H AGREED AND FELT THAT THE SMOKE THE OCCUPANTS SMELLED MAY BE A FAULTY APPLIANCE.