Case: T14DV02904

Parcel: 120051770


Addresses:

4556 S 12TH AV

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
05/07/2014 INSP - INITIAL CODE ENFORCMENT Approved THERE ARE TWO RECEPTACLE OUTLETS MOUNTED ON A DILAPIDATED POST WITH MULTIPLE SUPPORTING PIECES OF WOOD OR STEEL.
THE MAIN POST HAS MOVEMENT SO THERE HAS BEEN ROPE WRAPPED AROUND THE POST AND THE SUPPORTING MEMBERS SO HELP ELIMINATE THE MOVEMENT. THIS METHOD HAS FAILED.

THE OUTLET WITH THE 110 V DUPLEX RECEPTACLE IS NOT PROPERLY MOUNTED AND LOOSE, THE BOX EXTENSION HAS SEPARATED FROM THE MAIN BOX IS NOW NOT WEATHER PROTECTED, THE RECEPTACLE IS NOT GFCI TYPE. THIS JUNCTION BOX ALSO HAS ROPE WRAPPED AROUND IT FOR SUPPORT.

THE SECOND OUTLET HAS AND 30 AMP RECEPTACLE. THE RECEPTACLE IS LOOSE AND NOT PROPERLY SEATED OR PROTECTED. THIS JUNCTION BOX ALSO HAS ROPE WRAPPED AROUND IT FOR SUPPORT.

THE EXTENSION CORDS BEING BY USED BY THE PEDDLER HAVE SPLICES AND DEFECTS. AN INDOOR POWER STRIP IS BEING USED FOR THE FREEZER CONNECTED UNDER THE MESQUITE TREE. THE 30 AMP CORD IS POWERING THE FREEZER UNIT ON THE TRUCK.

THERE HAS BEEN AN INSTALLATION OF A PRIVATE METER AT THIS LOCATION.

THIS EQUIPMENT HAS BEEN INSTALLED ON THE VACANT LOT. THE SOLE PURPOSE AND USE FOR THIS EQUIPMENT AT THIS TIME IS FOR THE PEDDLER'S EQUIPMENT. THE EQUIPMENT ON THE VACANT LOT HAS NO OVER CURRENT PROTECTION DEVICE. THIS EQUIPMENT IS BEING FEED BY AN UNDERGROUND FEEDER FROM THE ADJACENT BUILDING WHICH IS ON A DIFFERENT PARCEL.

THIS EQUIPMENT WAS INSTALLED WITHOUT A PERMIT. THIS EQUIPMENT IS IN A HAZARDOUS STATE. THE INSTALLATION OF THIS EQUIPMENT IS NOT CODE COMPLIANT AND MUST BE REMOVED TO PREVENT FUTURE USE.

ACTION TAKEN BY THE CITY OF TUCSON.
I HAND DELIVERED THE NOTICE OF VIOLATION TO THE TENANT WITH INSTRUCTIONS TO GIVE TO THE OWNER; O DAYS TO UNPLUG ALL SPLICED AND DEFECTIVE EXTENSION CORDS. WITHIN 24 HOURS TO SHUT THE CIRCUIT BREAKERS OFF AND 10 DAYS TO REMOVE THE DILAPIDATED SYSTEM.