Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T14DV00828

Parcel: 12007054A


Addresses:

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
03/11/2014 INSP - INITIAL CODE ENFORCMENT Approved THE 60 AMP MAIN DISCONNECT HAS A BACK FED BREAKER WITH NO HOLD DOWN, NO DEAD FRONT, NO LABELING, THE NEUTRAL STRAND WIRE HAS BEEN CUT TO FIT IN THE LUG. THERE IS NEW EMT CONDUIT WITH INTERIOR FITTINGS.

A NEW 100 AMP PANEL HAS BEEN INSTALLED NEXT TO THE MAIN DISCONNECT WHICH HAS NO LABELING, UNUSED OPENINGS, NEW CONDUIT INSTALLED WITH WRONG TYPE OF PVC FITTINGS AND PIPE.

THE PVC CONDUIT RACEWAYS ARE NOT PROPERLY SECURED TO THE BUILDING. THERE ARE NEW BRANCH CIRCUITS INSTALL IN THE CARPORT AREA FOR A DRYER AND GENERAL USE RECEPTACLES IN THE CARPORT AND PORCH AREA. THE EASTSIDE OF THE BUILDING HAS EMT NOT PROPERLY INSTALLED SUPPLYING POWER TO A WINDOW MOUNT AC UNIT.
THE WESTSIDE OF THE BUILDING HAS AN INTERIOR TYPE BOX WHICH HAS A RECEPTACLE SUPPLYING POWER TO THE WASHING MACHINE, UNPROTECTED.

THE WEST SIDE OF THE BUILDING HAS A STAND PIPE FOR A WASHER INSTALLED INCORRECTLY TO THE BUILDING DRAIN WASTE VENT PIPE.

A NEW GAS FIRED WATER HEATER HAS BEEN INSTALLED OUTDOORS WITH NO ENCLOSURE PROTECTION, NO VENTING SYSTEM.

THE TOILET IS NOT PROPERLY ANCHORED TO THE TOILET FLANGE.
THE TANK IS CRACKED.

THE SHOWER HAS A BLOCKED IN THE DRAIN.

NO SMOKE DETECTORS IN THE DWELLING

BASE BOARD HEATER IS INOPERABLE

FRONT DOOR HAS NO WEATHER STRIPPING

THERE IS STORAGE OF CLOTHING AND MISCELLANEOUS ITEMS UNDER THE PORCH AND THE SIDES OF THE PROPERTY.

TRASH AND DEBRIS ON THE PROPERTY.