Description:

There are roaches throughout the house. The sink is leaking. Stove turns on by itself. The shower does not drain. Toilet leaks from under the commode.

Case Violations

Case Number: T14DV00828
Case Status: COMPLIAN
Case Description: MULTIPLE TYPES
Total Violations: 7
Violation Date Code Statue
03/11/2014 T.C. Ch. 16, Sec. 16-11(a)(3) Every existing dwelling unit shall be provided with smoke detectors in good operating condition as required by the Tucson Fire Code of the City of Tucson.
03/11/2014 T.C. Ch. 16, Sec. 16-11(b) (1) HEATING. Every habitable room within a dwelling unit, guest room, and congregate residence shall be provided with safe heating facilities which are properly installed and maintained in a sound condition and are capable of providing adequate heating, appropriate for the climate, to assure a safe living environment. All heating facilities shall be free from health hazards associated with ventilation, mounting, electrical and gas connections and other defects. Unvented fuel-burning heaters must be of a listed and approved type, and are prohibited as the sole source of heating. Ovens, stoves or ranges, or other cooking appliances cannot be used for the purpose of heating any portion of a dwelling. Listed, portable space heaters may only be used as the sole source of heating on a temporary basis when the permanent heating system is being repaired or replaced.
03/11/2014 T.C. Ch. 16, Sec. 16-4. PERMITS REQUIRED. Unless otherwise exempt pursuant to section 301 of the Administrative Code, as adopted by reference per section 6-1 of this Code, or pursuant to any other ordinance or statute, no building, structure or building service equipment regulated by this chapter or by the technical codes adopted by the city shall be built, erected, constructed, enlarged, altered, repaired, moved, improved, removed, converted or demolished unless a permit first has been obtained from the building official in the manner provided in the administrative and building codes adopted by the city. The purpose of a permit is to ensure that all construction is inspected by qualified City of Tucson personnel as directed by ordinance to verify compliance with city codes. Failure to obtain proper permit with inspections and approvals shall deem the construction to be unsafe.
03/11/2014 T.C. Ch. 16, Sec. 16-11(e) PLUMBING SYSTEMS. (4) All plumbing fixtures shall be connected to a public sewer system or to an approved private sewage disposal system, with the connections free from leaks, blockages, or other defects. All plumbing fixtures shall be connected to an approved system of water supply and provided with hot and cold running water necessary for its normal operation.
03/12/2014 T.C. Ch. 16, Sec. 16-12(a) EXTERIOR SURFACES. (1) Weather protection. All weather-exposed exterior surfaces of every building, including windows and doors, shall provide weather protection. Every building shall be weather protected to provide shelter for the occupants against the elements and to exclude moisture and dampness.
03/12/2014 T.C. Ch. 16, Sec. 16-13(h) OUTDOOR STORAGE Outdoor storage on residential properties is prohibited under the following conditions: 1. When stored in the front yard. 2. When stored in the side yard or rear yard and is not screened by a minimum five foot high solid wall or opaque fence. 3. When exceeds 25% of the total lot area. 4. When stored in an open covered porch that is visible from beyond the boundaries of the lot. 5. When stored in an open carport that is visible from beyond the boundaries of the lot where the amount of storage restricts an automobile from being properly stored within the carport. A double carport will require enough space to store two automobiles. 6. When storage items include garbage, refuse or debris.
03/12/2014 T.C. Ch. 16, Sec. 16-13(b) ACCUMULATION OF REFUSE PROHIBITED. Each owner, lessee, tenant, resident or occupant shall maintain a property so it is free of accumulated refuse and debris. Accumulated refuse and debris means contained or uncontained refuse and debris that is present on the property in a manner not authorized by the Tucson Code. Material recycling facilities meeting the requirements of section 15-24.7 are exempt from this prohibition.

Outstanding Inspections

Case Number: T14DV00828
Case Status: COMPLIAN
Case Description: MULTIPLE TYPES
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
04/23/2014 LUC - RESIDENTIAL STORAGE VALDEZ Item closed
04/23/2014 NPO(EL)-MAIN/PANEL/SUB/DISCONT VALDEZ Item closed
04/23/2014 NPO(EL)-WIRING/SWITCH/OUTLT/FX VALDEZ Item closed
04/23/2014 NPO(PL)-PLUMBING SYSTEM & FX VALDEZ Item closed
04/23/2014 NPO(PL)-WATER HEATERS VALDEZ Item closed
04/23/2014 NPO(HC)-HEATING & VENTILATION VALDEZ Item closed
04/23/2014 NPO - INSECTS/PESTS VALDEZ Item closed
04/23/2014 NPO - OTHER VALDEZ Item closed
04/23/2014 NPO - EXT. BUILDING MAINTENANC VALDEZ Item closed

Completed Inspections

Case Status: COMPLIAN
Case Number: T14DV00828
Case Description: MULTIPLE TYPES
Total Completed Inspections - 2
End Date Description Inspector Results Comments
03/11/2014 INSP - INITIAL CODE ENFORCMENT VALDEZ Approved THE 60 AMP MAIN DISCONNECT HAS A BACK FED BREAKER WITH NO HOLD DOWN, NO DEAD FRONT, NO LABELING, THE NEUTRAL STRAND WIRE HAS BEEN CUT TO FIT IN THE LUG. THERE IS NEW EMT CONDUIT WITH INTERIOR FITTINGS. A NEW 100 AMP PANEL HAS BEEN INSTALLED NEXT TO THE MAIN DISCONNECT WHICH HAS NO LABELING, UNUSED OPENINGS, NEW CONDUIT INSTALLED WITH WRONG TYPE OF PVC FITTINGS AND PIPE. THE PVC CONDUIT RACEWAYS ARE NOT PROPERLY SECURED TO THE BUILDING. THERE ARE NEW BRANCH CIRCUITS INSTALL IN THE CARPORT AREA FOR A DRYER AND GENERAL USE RECEPTACLES IN THE CARPORT AND PORCH AREA. THE EASTSIDE OF THE BUILDING HAS EMT NOT PROPERLY INSTALLED SUPPLYING POWER TO A WINDOW MOUNT AC UNIT. THE WESTSIDE OF THE BUILDING HAS AN INTERIOR TYPE BOX WHICH HAS A RECEPTACLE SUPPLYING POWER TO THE WASHING MACHINE, UNPROTECTED. THE WEST SIDE OF THE BUILDING HAS A STAND PIPE FOR A WASHER INSTALLED INCORRECTLY TO THE BUILDING DRAIN WASTE VENT PIPE. A NEW GAS FIRED WATER HEATER HAS BEEN INSTALLED OUTDOORS WITH NO ENCLOSURE PROTECTION, NO VENTING SYSTEM. THE TOILET IS NOT PROPERLY ANCHORED TO THE TOILET FLANGE. THE TANK IS CRACKED. THE SHOWER HAS A BLOCKED IN THE DRAIN. NO SMOKE DETECTORS IN THE DWELLING BASE BOARD HEATER IS INOPERABLE FRONT DOOR HAS NO WEATHER STRIPPING THERE IS STORAGE OF CLOTHING AND MISCELLANEOUS ITEMS UNDER THE PORCH AND THE SIDES OF THE PROPERTY. TRASH AND DEBRIS ON THE PROPERTY.
04/23/2014 INSP - FOLLOW UP CODE ENFORCE VALDEZ Approved TEP DID CUT POWER AT THE POLE, THE DWELLING IS VACANT AND SECURED. CLOSE CASE

Completed Activity Special Conditions

Case Description - MULTIPLE TYPES
Case Number - T14DV00828
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 5
Date Name
02/21/2014 CONTACTED BY PHONE
03/13/2014 CONTACTED BY MAILING
03/12/2014 CONTACTED BY EMAIL
03/13/2014 NOTICE OF VIOLATION ISSUED
04/25/2014 VIOLATION CLOSED