Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T14CM07545
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/27/2015 | FIRE - FINAL | Approved | ||
07/24/2015 | FIRE - FINAL | Partial Approval | 1. CAN NOT PERFORM ALARM FINAL TODAY - MUST RESCHEDULE WHEN SUBCONTRACTOR IS AVAILABLE AND BATTERIES ARE CHARGED ( SYSTEM NOT IN TROUBLE MODE) 2. CANT TEST DELAY ON DOORS UNTIL ALARM SYSTEM IS FUNCTIONING PROPERLY 3. EMERGENCY LIGHTING NOT OPERATING ( BATTERIES WERE SPENT IN LAST 3 DAYS OF POWER OUTAGE TO THE BUILDING) 4. SUB CONTRACTOR MUST CALL IN HIS FIRE ALARM FINAL |
|
07/09/2015 | FIRE - FINAL | Partial Approval | 1. Temp C of O OKAY for stocking no sales no public 2. Need 36 inches clearance around the FDC- IFC 912.3.2 3. All egress doors o that have delay egress operation shall have the following sign attached above the panic hardware device stating the following: "PUSH UNTIL ALARM SOUNDSDOOR CAN BE OPEND IN 15 SECONDS" Lettering shall be at least 1 inch height and shall have a stroke of not less than 1/8 inch on a contrasting background. 4. Need to install a fire dept. key box and have the FACP & main entrance door key 5. Front of the store eastside aisle one emergency light failed repair or replace 6. Exit door by golf putting holes panic hardware failed to work on 15 second delay need to repair or replace 7. Need to activate the alarm system to test delay by-pass on all exit doors that have the 15 second delay - need to make sure the delay shuts off and door operates with no delay. 8. Need all fire extinguishers signed so as that they can be found from any part on the building. 9. Need front egress emergency lighting working 10. Exit door pathway to exit door by golf putting section need to remove the hole in pathway no obstuctions |