Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T14CM07545
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/27/2015 | FIRE - ALARM FINAL | Approved | ||
07/24/2015 | FIRE - ALARM FINAL | Partial Approval | SUB CONTRACTOR DID NOT CALL IN ALARM FINAL. ALARM WAS IN TROUBLE MODE UPONE ARRIVAL AND CONTRACTOR STATES IT IS DUE TO A POWER OUTAGE OVER THE PAST FEW DAYS AND THE BATTERIES NOT BEING CHARGED ANYMORE. MUST CALL IN ALARM FINAL NEXT WEEK/ HAVE ALARM SUBCONTRACTOR AVAILABLE TO PERFORM A TEST ON THE SYSTEM AND ENSURE THAT DELAYED DOORS OPERATE IN THE 15 SECOND DELAY TIME PERIOD. |
|
07/09/2015 | FIRE - ALARM FINAL | Partial Approval | 1. All egress doors o that have delay egress operation shall have the following sign attached above the panic hardware device stating the following: "PUSH UNTIL ALARM SOUNDSDOOR CAN BE OPEND IN 15 SECONDS" Lettering shall be at least 1 inch height and shall have a stroke of not less than 1/8 inch on a contrasting background. 2. Exit door by golf putting holes panic hardware failed to work on 15 second delay need to repair or replace 3. Need to activate the alarm system to test delay by-pass on all exit doors that have the 15 second delay - need to make sure the delay shuts off and door operates with no delay. |