Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T14CM07269
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/10/2014 | FIRE - FINAL | Approved | ||
11/06/2014 | FIRE - FINAL | Denied | 1. Need to correct sprinkler coverage in hall way to storage rooms sprinkler cannot be more than 7' 6" off a wall right head is 10' 6" off wall. 2. Need annual sprinkler inspection done 3. Need 5 year check valve done 4. Need suite numbers on back door 3" size 5. Repair or replace exit sign battery backup failed 6. Fire extinguisher need 2A-10BC type (1) 7. Cannot open breaker panel door to inspect repair 8. Outlet box below breaker panel missing cover plate |