Permit: T14CM07269

Parcel: 125121110

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
11/10/2014 FIRE SPKLR - FINAL Approved
11/06/2014 FIRE SPKLR - FINAL Denied 1. Need to correct sprinkler coverage in hall way to storage rooms sprinkler cannot be more than 7' 6" off a wall right head is 10' 6" off wall.
2. Need annual sprinkler inspection done
3. Need 5 year check valve done