Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/29/2017 | FIRE - FINAL | Approved | ||
| 08/17/2017 | FIRE - FINAL | Partial Approval | Fire Sprinkler Approved Kitchen Fire System Approved Fire Alarm Approved per the submitted drawings minus the smoke control 3rd party approval. All controls and activation of the smoke control system operated properly. On field verification it was found that they needed to add four horn smoke detectors and sounders. Asked that they add the fire sprinkler panel in the FCC. Emergency and Exit lights will be completed by September. Signs for everything must be installed. System was left "Active" as of today. Ok for certifcate or Letter of TCO |