Permit: T14CM04154

Parcel: 12810069A


Addresses:

436 S WILLIAMS BL


Inspection Status: Approved

Inspection History: FIRE SPKLR - UG, PIPING, HYDRO

Permit Number - T14CM04154

Inspection Description - FIRE SPKLR - UG, PIPING, HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
03/17/2015 FIRE SPKLR - UG, PIPING, HYDRO Approved Ductile iron is covered, joints have megalugs ( felt under the plastic covering), 200 psi since 6 AM ( recorded at 10:26 AM), no leaks, built as per approved plans. City already back filled over their portion where it ties into permitted portion.
NS / 3/17/15
03/04/2015 FIRE SPKLR - UG, PIPING, HYDRO Cancelled Called and talked to the contractor on site and asked him if they have a separate plan and permit for the UG he stated that need to cancel and he will have someone in first thing in the morning with a plan and get a permit.