Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T14CM04154
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/18/2015 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
08/18/2015 | MECHANICAL - FINAL | Approved | WILL CHECK AIR BALANCE AT BUILDING FINAL | |
08/12/2015 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
08/12/2015 | MECHANICAL - FINAL | Partial Approval | VACUUM BREAKER AT MOP SINK SOAP DISPENSER CANNOT BE UNDER CONSTANT PRESSURE. EXTEND GREASE DUCT WITH 16 GA METAL AT BBQ. PROVIDE RATED GASKET. NEED AIR BALANCE REPORT | |
08/03/2015 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
08/03/2015 | MECHANICAL - FINAL | Partial Approval | FIRE WRAP MUST EXTEND 18" UP INTO CURB AND BAND (?) AT TOP. ACCESS DOORS NOT PER SPECS. ADD MORE BANDS. OVERLAPS MUST BE MIN 3". ADD A CLEANOUT ON DUCT ON ROOF. FAN EXTENSION TO BE ???. | |
07/15/2015 | MECHANICAL - FINAL | Not ready for Inspection | NOT READY- BBQ WELD LEAKS ON SMOKE TEST |