Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/18/2015 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection :* |
| 08/18/2015 |
MECHANICAL - FINAL |
|
Approved |
WILL CHECK AIR BALANCE AT BUILDING FINAL |
| 08/12/2015 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection :* |
| 08/12/2015 |
MECHANICAL - FINAL |
|
Partial Approval |
VACUUM BREAKER AT MOP SINK SOAP DISPENSER CANNOT BE UNDER CONSTANT PRESSURE. EXTEND GREASE DUCT WITH 16 GA METAL AT BBQ. PROVIDE RATED GASKET. NEED AIR BALANCE REPORT |
| 08/03/2015 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection :* |
| 08/03/2015 |
MECHANICAL - FINAL |
|
Partial Approval |
FIRE WRAP MUST EXTEND 18" UP INTO CURB AND BAND (?) AT TOP. ACCESS DOORS NOT PER SPECS. ADD MORE BANDS. OVERLAPS MUST BE MIN 3". ADD A CLEANOUT ON DUCT ON ROOF. FAN EXTENSION TO BE ???. |
| 07/15/2015 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
NOT READY- BBQ WELD LEAKS ON SMOKE TEST |