Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
Permit Number - T14CM04154
Inspection Description - MECHANICAL - HOODS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/12/2015 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* | |
08/10/2015 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* | |
08/10/2015 | MECHANICAL - HOODS | Partial Approval | PROVIDE A HINGE KIT AT EX. FAN INSULATION PINS MISSING AT GREASE DUCT CLEANOUT. EXTEND SEWER VENTS 2' ABOVE AIR INTAKES. 1/2" I.D. X 12" GAS FLEX NOT ADEQUATE FOR 250,000 BTU. PROVIDE PROTECTION AT SEAL TITE TO EXHAUST FAN | |
08/03/2015 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* | |
07/27/2015 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* | |
07/21/2015 | MECHANICAL - HOODS | Partial Approval | WHERE IS THE COLLAR TO CONNECT DUCT TO FAN SMOKE TESTED B.B.Q GREASE DUCT. OK TO DOUBLE WRAP. PROVIDE AN APPROVED CLEAN OUT AT KITCHEN EXHAUST DUCT ON ROOF. PROVIDE LISTING FOR CANVAS CONNECTOR. |