Permit: T14CM04154

Parcel: 12810069A


Addresses:

436 S WILLIAMS BL


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T14CM04154

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/06/2015 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/16/2015 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/16/2015 ELECTRIC - INTERMEDIATE Partial Approval BATHROOMS WESTSIDE, MEETING ROOM, AND TRAINING ROOM 1 AND 2 OK
03/27/2015 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/27/2015 ELECTRIC - INTERMEDIATE Partial Approval 1. BELL ENDS ON PVC PIPE FROM TRANSFORMER TO SWITCH GEAR. TRENCH HAS 3 3" PVC, OK
2. FROM SWITCH HEAR 1 2" PVC TO SUB-PANEL TRENCH OK
3. NEED TWO GROUND RODS AT SUB-PANEL
12/22/2014 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
12/22/2014 ELECTRIC - INTERMEDIATE Partial Approval 2 1/2" CONDUIT FEEDER LINES FOR 4 PANELS OF EAST & MIDDLE PORTION OF BUILDING - OK TO COVER PROGRESS AREAS