Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/18/2015 | FRAMING | Approved | IVRS - Inspection :* | |
| 02/10/2015 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 12/30/2014 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 12/30/2014 | FRAMING | Denied | ALL BEDROOM WINDOWS TO MEET EGRESS REQUIREMENTS MIN 20"X30" NET OPEING. 5.4 (?) HEIGHT NOT TO EXCEED 44" 1. BLOCK BOOTS 3-SIDES 2. 14-3 SMOKE ALARM CIRCUIT 3. PROVIDE DEDICATED 20 AMP FRIDGE CIRCUIT 4. EGRESS WINDOWS PROVIDE MIN 20"X30" NET OPENING 5.4 (?) HEIGHT NOT TO EXCEED 44" 5. BED 2 MISSING OUTLET NORTH WALL, EXPOSED HOMERUNS. FIREBLOCK DROPPED CEILING 6. MISSING DRYER VENT 7. EXHAUST FAN BATH 8. BLOCK TUB WALLS. GROUT TUB SHOE 9. RELOCATE CONDENSOR DISCONNECT 10. GROUND METAL BOXES 11. TERMINATE CONDENSATE LINE TO EXTERIOR 12. 10-3 WATER HEATER CIRCUIT |
|
| 11/25/2014 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
| 07/14/2014 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
| 07/14/2014 | FRAMING | Not ready for Inspection | NEXT NOT READY MAY RESULT IN A REFEE | |
| 07/03/2014 | FRAMING | Not ready for Inspection | IVRS - Inspection :* |