Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2014 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* | |
| 08/22/2014 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* | |
| 08/20/2014 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* | |
| 08/19/2014 | MECHANICAL - HOODS | Partial Approval | 1.ALL TYPE 1 GREASE DUCT SMOKE/LEAK TEST OK INCLUDING 2 CLEANOUTS | |
| 08/06/2014 | MECHANICAL - HOODS | Partial Approval | 1 F.R.P IS COMBUSTIBLE EXTEND STAINLESS PANELS 18" BEYOND HOOD 2. EQUIP ITEM #1 IS A DOUBLE STACK PER SUBMITALS TYPE 2 HOOD REWUIRED (PLAN SHOWS SINGLE) |
|
| 08/05/2014 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* | |
| 08/05/2014 | MECHANICAL - HOODS | Partial Approval | 2 SECTION AREAS DUCT SMOKE TEST OK |