Permit: T14CM02524

Parcel: 117131600


Addresses:

160 S SCOTT AV

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
08/25/2014 MECHANICAL - HOODS Approved IVRS - Inspection :*
08/22/2014 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*
08/20/2014 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*
08/19/2014 MECHANICAL - HOODS Partial Approval 1.ALL TYPE 1 GREASE DUCT SMOKE/LEAK TEST OK INCLUDING 2 CLEANOUTS
08/06/2014 MECHANICAL - HOODS Partial Approval 1 F.R.P IS COMBUSTIBLE EXTEND STAINLESS PANELS 18" BEYOND HOOD
2. EQUIP ITEM #1 IS A DOUBLE STACK PER SUBMITALS TYPE 2 HOOD REWUIRED (PLAN SHOWS SINGLE)
08/05/2014 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
08/05/2014 MECHANICAL - HOODS Partial Approval 2 SECTION AREAS DUCT SMOKE TEST OK