Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/11/2015 | FIRE - FINAL | Approved | Per Ken B. fire issues completed for main bldg only, but believes some DSD issues still present. | |
| 10/09/2014 | FIRE - FINAL | Partial Approval | Temporary C of O for 30 days ok. Still need stairs/handrail fixed per Building Inspector. | |
| 10/08/2014 | FIRE - FINAL | Denied | REINSPECTION WILL OCCUR AT 12PM ON 10/9. 1. REMOVE ALL FLAMMABLE AND/OR COMBUSTIBLE GASES AND LIQUIDS FROM BUILDING. 2. REMOVE EXIT SIGNS THAT ARE LOCATED ABOVE SLIDING DOORS. THESE ARE NOT APPROVED EXIT DOORS. 3. LOWER FIRE EXTINGUISHERS SO THE TOP IS NO HIGHER THAN 5 FEET. 4. POST MAXIMUM OCCUPANT LOAD SIGN PER PLANS |
|
| 08/27/2014 | FIRE - FINAL | Not ready for Inspection | Until all life safety items including the fire sprinkler system, the manual fire alarm system and emergency lighting have been permitted and installed, TFD will not need to conduct a Fire Final Inspection for this Building Permit. We are still waiting for a plan submittal for the Manual Fire Alarm System. |