Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/12/2014 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection :* |
| 06/12/2014 |
MECHANICAL - FINAL |
|
Approved |
AIR BALANCE OK. LETTER FROM ENGINEER OK. PERMANENTLY I.D. EQUIPMENT ON ROOF. MARK DATA PLATES & FUSE ACCORDINGLY. REPAIR VANDALIZED GROUNDING ELECTRODE CONDUCTOR. OK FOR TEMP C OF O. |
| 06/11/2014 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection :* |
| 06/03/2014 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* |