Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/12/2014 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection :* |
| 06/11/2014 |
PLUMBING - FINAL |
|
Partial Approval |
IVRS - Inspection :* |
| 06/11/2014 |
PLUMBING - FINAL |
|
Partial Approval |
STERILIZATION REPORT IS OK. PROVIDE AIR BALANCE REPORT. NEED CAPTURE & CONTAINMENT TEST. STEAM FROM FAT FRYER IS NOT BEING CAPTURED PROPERLY. NEED TO TEST HEAT SENSORS. 3 COMPARTMENT SINK DRAINS TO BE INDEPENDANT & INDIRECTLY DRAINED. PROVIDE A LETTER FROM ENGINEER TO DELETE WATER CIRCULATING PUMP. PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX. CONDENSOR OVERFUSED. TERMINATE CONDENSATE PER PLAN. PAINT ALL EXPOSED PVC W/ LATEX PAINT. PERMANENTLY ID ALL EQUIPMENT ON ROOF. MARK A/C UNIT DATA PLATES WITH PROPER HEAT STRIP & FUSE ACCORDINGLY. LIST MAY NOT BE COMPLETE. |
| 06/03/2014 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* |