Permit: T13OT01000

Parcel: 115051500

Inspection Status: Denied

Inspection History: FIRE - FINAL

Permit Number - T13OT01000

Inspection Description - FIRE - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
09/05/2013 FIRE - FINAL Denied 1. need to have a type 1 hood this needs to be inspected by mechanical ispector to verify that the hood is a type one hood and is an approved hood before you install the ul 300 extinguishing system.

2. need a ul 300 system under hood this is currently a dry chem.
3. need suit numbers on outside.
4. ifc 2012 section 1104.13 hand rails are required on stairs at rear exit.
5. need to have a new set of plans that reflect the building far west side of restraunt is not on plans.
6. ifc 2012 section 1104.10 dimensions for existing stairs in buildings shall be permitted to remain if the rise does not exceed 8 1/4 inches 210mm and the run is not less than 9 inches