Case: T13DV03367

Parcel: 116162460


Addresses:

1027 N MAIN AV

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
05/17/2013 INSP - INITIAL CODE ENFORCMENT Approved Inspection due to minimum housing complaint: Site is zoned commercial; was previously a roofing company. Living unit converted from office space. Kitchen sink is not functional and does not have running water. No hot water, no hot water heater. HVAC mini split in living space installed without permit. Several vents in unit blocked, no functioning smoke alarms. Several electrical circuits and fixtures added without permit and do not appear to be to adopted code in most cases. Back room (south) wall where a subpanel is located is dilapidated and lacks proper finishing. Ceiling is damaged and dilapidated in several areas. Front addition added without permit. The lot also has 9 metal storage containers (7 over 200 sq. ft) each with added electrical all done without permits. Two ramadas have been erected between 3 units, over 200 sq. ft. No zoning compliance review on file for storage and residential use of property. A permit for a 200 amp main panel upgrade was finaled, but this did not include inspections of the interior electrical or added electrical to storage units (most storage units added after 2008).