Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T13CM07461
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/28/2014 | FIRE - FINAL | Approved | ||
09/09/2014 | FIRE - FINAL | Denied | 1. Need annual fire extingushers inspection completed 2. Need an annual sprinkler inspection completed 3. Need 5 year check valve completed 4. 1st floor heads to far from trusses need to 1 to 6 inches from truss some are 8 to 10 inches from trusses. 5. Clean out riser area not to be used as a storage room 6. Clean mechanical room on 2nd floor this room is not to be used as a storage room. (this is where the communications radio for alarm is located) |