Permit: T13CM07461

Parcel: 117110730


Addresses:

160 E ALAMEDA ST

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
10/28/2014 FIRE SPKLR - FINAL Approved
09/09/2014 FIRE SPKLR - FINAL Denied 1. 1st floor heads to far from trusses need to 1 to 6 inches from truss some are 8 to 10 inches from trusses.
2. Clean out riser area not to be used as a storage room
3. Clean mechanical room on 2nd floor this room is not to be used as a storage room. (this is where the communications radio for alarm is located)