Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/28/2014 | FIRE SPKLR - FINAL | Approved | ||
| 09/09/2014 | FIRE SPKLR - FINAL | Denied | 1. 1st floor heads to far from trusses need to 1 to 6 inches from truss some are 8 to 10 inches from trusses. 2. Clean out riser area not to be used as a storage room 3. Clean mechanical room on 2nd floor this room is not to be used as a storage room. (this is where the communications radio for alarm is located) |