Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/28/2014 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/23/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 12/23/2013 | ELECTRIC - FINAL | Denied | #8 COPPER WIRE ONLY RATED FOR 50 AMP. PROTECT WIRE AT ITS AMPACITY. VERIFY GAS/WATER BOND. VERIFY CONDUIT FILL HAS NOT BEEN EXCEEDED ON 1 1/4 EMT. CANNOT USE OLD METER SOCKET BASE AS RACEWAY TO JUNCTION BOX. PROTECT ANY SE CABLE UP TO 8' ABOVE GRADE. |