Permit: T13CM04494

Parcel: 11310001A


Addresses:

1545 E COPPER ST 01


Inspection Status: Approved

Inspection History: FIRE SPKLR - UG, PIPING, HYDRO

Permit Number - T13CM04494

Inspection Description - FIRE SPKLR - UG, PIPING, HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
01/27/2014 FIRE SPKLR - UG, PIPING, HYDRO Approved
01/13/2014 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval Okay to bury FDC piping - wire and wrap in place for 100 feet of pipe at the end where it turns toward to mountain road.
Note: TFD did not see piping that was added between this inspection from last inspection (12.26.2013) 100 feet of pipe for the FDC connection coming from copper road all already buried still need to test all piping at 200 PSI for 2 hours.

Also need to install underground shut off valve between fire hydrant and building to be sprinkle so as if butterfly valve on riser fails to shut down,TFD will not lose water to the fire hydrant for coverage when water on this line is shut down to replace valve.
12/30/2013 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval 140' feet tested from the road on Copper (FDC line) 200 psi for 2 hours approved. All wrapped and tracer wire installed.
12/26/2013 FIRE SPKLR - UG, PIPING, HYDRO Not ready for Inspection Did not have trench open yet