Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - UG, PIPING, HYDRO
Permit Number - T13CM04494
Inspection Description - FIRE SPKLR - UG, PIPING, HYDRO
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/27/2014 | FIRE SPKLR - UG, PIPING, HYDRO | Approved | ||
| 01/13/2014 | FIRE SPKLR - UG, PIPING, HYDRO | Partial Approval | Okay to bury FDC piping - wire and wrap in place for 100 feet of pipe at the end where it turns toward to mountain road. Note: TFD did not see piping that was added between this inspection from last inspection (12.26.2013) 100 feet of pipe for the FDC connection coming from copper road all already buried still need to test all piping at 200 PSI for 2 hours. Also need to install underground shut off valve between fire hydrant and building to be sprinkle so as if butterfly valve on riser fails to shut down,TFD will not lose water to the fire hydrant for coverage when water on this line is shut down to replace valve. |
|
| 12/30/2013 | FIRE SPKLR - UG, PIPING, HYDRO | Partial Approval | 140' feet tested from the road on Copper (FDC line) 200 psi for 2 hours approved. All wrapped and tracer wire installed. | |
| 12/26/2013 | FIRE SPKLR - UG, PIPING, HYDRO | Not ready for Inspection | Did not have trench open yet |