Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T13CM04373
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/28/2014 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
01/28/2014 | ELECTRIC - FINAL | Denied | PROVIDE RAIN-TIGHT FITTINGS ON EXTERIOR RACEWAYS. PROVIDE DEAD FRONT ON JUNCTION PANEL. CHECK BREAKER SIZE. PROTECT CONDUCTORS AT THEIR AMPACAITY. ISOLATE NEUTRALS AT SUBPANEL. UNABLE TO CHECK FUSE SIZE AT MAIN BREAKER "PANEL LOCKED." I.D. MAIN PANEL. REPLACE GAS/WATER BOND AND UFER. INCOMPLETE INSPECTION. DEMO OLD METER SOCKET. | |
07/19/2013 | ELECTRIC - FINAL | Not ready for Inspection | 1. Have a licensed electrician look at wiring and panels. Will require covers and approved wiring. |