Inspection History: ELECTRIC - CONSTRUCTION POWER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/18/2014 | ELECTRIC - CONSTRUCTION POWER | Approved | IVRS - Inspection :* | |
| 12/12/2013 | ELECTRIC - CONSTRUCTION POWER | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 12/12/2013 | ELECTRIC - CONSTRUCTION POWER | Partial Approval | OK TO CLEAR TEMP POWER. GROUND RODS NOT REQUIRED FOR UFER SYSTEM | |
| 12/12/2013 | ELECTRIC - CONSTRUCTION POWER | Denied | 1. SERVICE INSTALL NOT TO PRINT 2. 110.32 DOOR TO OPEN 90 DEGREES 3. 314.23 J BOX TO BE ANCHORED TO WALL 4. GROUND RODS MISSING, WATER & GAS BOND MISSING TOO 5. RISER STRAPPING MINI IS NOT LISTED |
|
| 12/05/2013 | ELECTRIC - CONSTRUCTION POWER | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 12/05/2013 | ELECTRIC - CONSTRUCTION POWER | Denied | 1. PROVIDE PROPER (SIZED) ROOF JACK AT PENETRATION 2. PROVIDE 2 POINTS OF ATTACHMENT AT RISER TO BUILDING |
|
| 10/25/2013 | ELECTRIC - CONSTRUCTION POWER | Not ready for Inspection | IVRS - Inspection :* |