Permit: T13CM02853

Parcel: 125060480


Addresses:

2117 E 4TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - CONSTRUCTION POWER

Date Description Inspector Results Comments
02/18/2014 ELECTRIC - CONSTRUCTION POWER Approved IVRS - Inspection :*
12/12/2013 ELECTRIC - CONSTRUCTION POWER Denied IVRS - Inspection :
See detailed listing on site.| 999*
12/12/2013 ELECTRIC - CONSTRUCTION POWER Partial Approval OK TO CLEAR TEMP POWER. GROUND RODS NOT REQUIRED FOR UFER SYSTEM
12/12/2013 ELECTRIC - CONSTRUCTION POWER Denied 1. SERVICE INSTALL NOT TO PRINT
2. 110.32 DOOR TO OPEN 90 DEGREES
3. 314.23 J BOX TO BE ANCHORED TO WALL
4. GROUND RODS MISSING, WATER & GAS BOND MISSING TOO
5. RISER STRAPPING MINI IS NOT LISTED
12/05/2013 ELECTRIC - CONSTRUCTION POWER Denied IVRS - Inspection :
See detailed listing on site.| 999*
12/05/2013 ELECTRIC - CONSTRUCTION POWER Denied 1. PROVIDE PROPER (SIZED) ROOF JACK AT PENETRATION
2. PROVIDE 2 POINTS OF ATTACHMENT AT RISER TO BUILDING
10/25/2013 ELECTRIC - CONSTRUCTION POWER Not ready for Inspection IVRS - Inspection :*