Inspection History: FIRE - FINAL

Permit Number - T13CM02748

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/31/2014 FIRE - FINAL Approved
07/21/2014 FIRE - FINAL Partial Approval FIRE IS ACCEPTABLE IF THE OWNER NEEDS TO START MOVING IN FURNITURE WITH BUILDING DEPARTMENT'S APPROVAL.
THE FOLLOWING ITEMS STILL NEED TO BE CORRECTED.
1. POST ADDRESS #
2. CLEAR ALL EXIT PATHS AND CORRIDORS.
3. INSTALL ALL HANDRAILS IN STAIRS
4. ADD EXIT SIGN AT EGRESS DOOR AT LEVEL 1 IN SOUTH STAIR. JUST LIKE THE ONE THAT WAS ADDED IN THE NORTH STAIR
5. ADD FIRE SPRINKLER COVERAGE IN ELECTRICAL ROOM WHERE PAN WAS ADDED-COVERAGE IS NEEDED BELOW THIS OBSTRUCTION
6. FINISH PAVERS FOR EGRESS FROM THE EXITS TO THE PUBLIC WAY
7. INSTALL ELEVATOR KEY BOX IN LOBBY NEAR ELEVATORS
8. ALL ELEVATORS SHALL BE ON AND WORKING
9. DO NOT BLOCK OPEN ANY FIRE RATED DOORS.
10. ELIMINATE LOCKING DEVICE (SLIDE BOLT) ON DOOR IN ELECTRICAL ROOM THAT HAS PANIC HARDWARE
11. FIRE DEPARTMENT WILL CONTACT BUILDING DEPARTMENT TO DETERMINE THE USE OF ELECTROMAGNETICALLY LOCKED EGRESS DOORS IN THE GROUP S OCCUPANCY AND THEIR COMPLIANCE WITH 1008.1.9.9 OF THE IBC/IFC
07/15/2014 FIRE - FINAL Denied STILL NEED TO TEST CO FOR GARAGE UNDER EMERGENCY POWER WITH ALL THE LIFE SAFETY SYSTEMS.
MAGNETIC LOCKS SHALL BE INSTALLED FOR TESTING
ALL FIRE DOORS SHALL BE COMPLETED
KEY BOX FOR ELEVATOR NEEDS TO BE INSTALLED
INSTALL EXIT SIGN AT BOTTOM OF STAIRS
07/15/2014 FIRE - FINAL Partial Approval STAIR PRESSURIZATION REPORTS ACCEPTED. FANS AND SUPPLY MEET PLAN SPECIFICATIONS AND PRESSURIZATION REQUIREMENTS FOR ALL LEVELS.