Permit: T13CM01537

Parcel: 133231910

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T13CM01537

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/07/2014 BUILDING - FINAL Approved IVRS - Inspection :*
02/27/2014 BUILDING - FINAL Partial Approval IVRS - Inspection :*
02/12/2014 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
02/12/2014 BUILDING - FINAL Not ready for Inspection PROVIDE CITY APPROVED REVISIONS. INSTALL RO DRAIN THRU AIR CAP AND CONNECT INDIRECTLY TO SINK TAIL PIECE (CORRECT DRAIN). CLIP FRONT SIDE OF SINK. SECURE DW. MV ASSLE 1070 SHOWN DETAIL 208 P-4. INTERNAL BACKFLOW ASSEMBLIES REQ TEST AFTER UPSTREAM WORK. A/C UNIT FILTERS NOT FITTING. INSTALL ACCESS DOOR. HOLE IN MAKEUP AIR DUCT. INTERLOCK RESTROOM FAN W/ FC2 PER PLAN. COMPLETE CONDENSATE TO DRY WALL ON EASTSIDE COL. PATIENT ROOMS REQ SPECIAL OUTLETS. NEC DRT (?) 517 OUTLETS AT RS REQ GFI. PROVIDE DEDICATED OUTLETS BELOW LAVITORY OR GFI.
12/30/2013 BUILDING - FINAL Partial Approval OK TCO PER DISCUSSION WITH BRIAN. MINOR ITEMS AND PERMIT CLEAN-UP REMAIN