Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T13BU01132
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/21/2013 | FIRE - KITCHEN EXH HOOD FINAL | Approved | ||
10/18/2013 | FIRE - KITCHEN EXH HOOD FINAL | Denied | Did test the last link on line trip and pull station trip - All passed All nozzles, links and coverage per approved plans. K - class fire extinguisher on site 1. Need splash guard on both sides of fryer for protection from open flames 2. No gas, not able to test gas line shut off valve |